Sound quality control method of 110 kV transformer based on distributed variable stiffness dynamic vibration absorber

Read the full article See related articles

Listed in

This article is not in any list yet, why not save it to one of your lists.
Log in to save this article

Abstract

Using the A-weighted sound pressure level ( L A ) as the only evaluation index for transformer noise is unreasonable. To measure the actual impact of transformer noise on humans more effectively, this paper proposes to introduce the sound quality evaluation method into the evaluation of transformer noise. First, the field noise of a 110 kV transformer was measured, and the objective parameters and subjective scores of the noise samples were analyzed, and a subjective prediction model of sound quality was established using the multiple linear regression method. Subsequently, a sound quality control methodology was proposed, which targets noise attenuation at the 100 Hz fundamental frequency and its first six harmonic components, while excluding non-peak frequency bands, and its effectiveness was verified. Additionally, a distributed variable stiffness dynamic vibration absorber (DVA) was designed to mitigate structural-borne noise and improve sound quality. Laboratory experiments quantified its vibration and noise reduction efficacy: with a single-DVA configuration, vibration reduction rate was over 30%, while the noise level decreased by ≥ 1 dB. Finally, a field noise measurement was carried out. The results demonstrate that the subjective score was improved from 4.7 to 6.1, meaning that subjective feelings were improved by two levels.

Article activity feed