Impact of Ventilation Performance on Human Behaviour: A Case Study After Apartment Building Thermo-Modernization

Read the full article See related articles

Listed in

This article is not in any list yet, why not save it to one of your lists.
Log in to save this article

Abstract

Increasing requirements for reducing energy consumption result in thermo-modernisation existing buildings. Modernized buildings have significantly lower transmittation coefficient; infiltration air rate slows down markedly, which may lower indoor air quality (IAQ) noticeable; one gauge with a vane probe measures the air velocity and temperature at a grille in the toilet; second gauge with IAQ probe located in a room measures the mole fraction of carbon dioxide, dry-bulb and wet-bulb temperatures, absolute pressure, and humidity; moreover there are estimated the measurements uncertainties of: the volume flow rate, mole fraction of CO2, temperatures, and humidity. IAQ in a dwelling after thermo-modernization is evaluated in a sixty-year old building; heating system ensures thermal comfort during heating season; ventilation performs poorly, for vapor condenses on the window; carbon dioxide concentration is too high, which curbs mental activity greatly.